Free-cooling chillers for data centers

23 of 32 vendors offer free cooling, built in or as an add-on module. 17 of them also use oil-free compressors, 20 sell air-cooled units and the highest supply water stated is 35 °C (Carrier). Compare the supply temperature and the capacity range before the free-cooling label.

23 of 32 vendorsChecked

Heat rejectionCompressorsRefrigerantsEfficiency (as published)
Trane400121,0002Air- and water-cooledOil-free magnetic-bearing centrifugal; centrifugal; variable-speed screwR-1234ze; R-513A; R-134a; R-1233zd; R-515B—GVAF: SEER up to 6.55; seasonal metric, not full-load EER2026-11-11
Daikin Applied302110,5511Air- and water-cooledVariable-volume-ratio screw; Variable-speed oil-free magnetic-bearingR-1234ze(E); R-515B; R-513A; R-1233zd(E)29.41Pathfinder AWV: IPLV above 22 EER; Pathfinder AWM: up to 22.7 IEER (US units)2026-11-11
Vertiv30016,0004Air- and water-cooledInverter screw; oil-free magnetic-levitation centrifugalR-1234ze; R-513A; R-515B; R-134a——2026-11-11
Carrier17013,8001Air- and water-cooledScroll; variable-speed screw; two-stage magnetic-bearing centrifugalR-513A; R-1234ze(E); R-515B; R-32353COP 6.75, IPLV 11.4 under AHRI (AquaEdge 19MV4)2026-11-11
Multistack—2,9891Air-cooledTwo-stage variable-speed centrifugal MagLev———2026-11-11
Smardt21112,5001Air- and water-cooledOil-free magnetic-bearingR-513A; R-515B; R-1234ze; R-134a——2026-11-11
Uniflair (Schneider Electric)1,20012,5001Air-cooledOil-free magnetic-bearing centrifugal—331EER 4.66 (Schneider Electric’s figure; rating conditions not published)2026-11-11
APX DCS (LFB Group)5012,4001—Oil-free centrifugal; multi-scroll; inverter screwR-1234ze; R-454B——2026-11-11
Midea Building Technologies56312,2511Air-cooledTwo-stage magnetic-bearing centrifugal; inverter screwR-1234ze(E); R-513A—COP up to 7.11 at AHRI conditions (centrifugal line)2026-11-11
Geoclima (Munters)—2,2001Air-cooledOil-free centrifugal Turbocor with magnetic levitationR-513A; R-134A; R-1234ze—R513A/R134A example: full-load EER 5.35 at 35°C ambient and 34/24°C water2026-11-11
LG Electronics1,68812,1101Air-cooledSemi-hermetic oil-free magnetic-bearing centrifugal, variable-speedR-513A—EER 4.0 at full load, microchannel heat exchanger2026-11-11
Airedale by Modine11012,0002Air-cooledOil-free centrifugal TurbocorR-1234ze; R-134a262Up to 39% energy savings over standard methods (TurboChill DCS, vendor claim)2026-11-11
ENGIE Refrigeration25012,0001Air- and water-cooledOil-free magnetic-bearing———2026-11-11
STULZ28011,8601Air- and water-cooledScrew (stepless or frequency-converter); TurbocorR-1234ze; R-513A251—2026-11-11
Kaltra25011,8501Air-cooledScrew; scrollR-134a; R-513A; R-1234ze; R-410A; R-452B; R-454B——2026-11-11
Mitsubishi Electric (Climaveneta)1,20011,7501Air-cooledMagnetic-levitation centrifugal; oil-free magnetic-bearingR-1234ze; R-515B263—2026-11-11
Aermec20011,6001Air-cooledScrew (NSM HWT); Turbocor magnetic-levitation (TBA/TBG)R-134a; R-513A; R-1234ze; R-515B; R-32301—2026-11-11
Motivair by Schneider Electric3511,5831—Screw and scroll optionsR-134a; R-410A; R-1234ze; R-513A——2026-11-11
Euroklimat19011,4001Air- and water-cooledOil-free magnetic-levitation TurbocorR-134a; R-513A; HFO option——2026-11-11
Galletti37011,2001Air-cooledHermetic scrollR-410A——2026-11-11
Swegon (BlueBox)22014801Air-cooledScrollR-32201—2026-11-11
Clivet——Air-cooledMagnetic, full inverter———2026-11-11
Mitsubishi Heavy Industries Thermal Systems———Centrifugal———2026-11-11

The lines behind each row

All 32 vendors

How to read the columns

Methodology
Smallest unit kW
Lowest published cooling capacity across the chiller lines named in the 'Lines' field, converted from refrigeration tons at 3.517 kW per ton where the vendor publishes tons. Rating conditions differ by vendor and line, so compare ranges, not decimals. Blank when no line states a lower bound.
Largest unit kW
Highest published cooling capacity of a single chiller across the lines named in 'Lines', converted from tons at 3.517 kW per ton where needed. Project totals, multi-unit plants and announced-only products are excluded. Blank when not published.
Heat rejection
How the named lines reject heat: air-cooled (condenser fans), water-cooled (cooling tower or dry cooler loop) or both. Absorption chillers run on a heat source instead of an electric compressor.
Compressors
Compressor technologies in the named lines, as the vendor words them: scroll, screw, centrifugal, magnetic-bearing (oil-free) centrifugal.
Refrigerants
Refrigerants the vendor lists for the named lines. A refrigerant may be offered only on some sizes or markets; the record's sources say which.
Max supply water °C
Highest chilled-water supply (leaving) temperature the vendor states for a named line. A rating point is not an operating limit and is not used here. Blank when not stated.
Efficiency (as published)
Efficiency figures with the metric and conditions the vendor gives (EER, SEER, IPLV, COP). The metrics are not interchangeable: SEER and IPLV are weighted part-load figures, EER and COP are single points.