Air-cooled data center chillers

23 of 32 vendors sell air-cooled chillers for data centers. 20 of them offer free cooling, 19 use oil-free compressors and 17 offer an HFO or natural refrigerant. The warmest supply water stated is 35 °C (Carrier). Capacity ranges below cover every line a vendor lists, water-cooled lines included.

23 of 32 vendorsChecked

CompressorsRefrigerantsFree coolingAI or high-density claim
Trane400121,0002Oil-free magnetic-bearing centrifugal; centrifugal; variable-speed screwR-1234ze; R-513A; R-134a; R-1233zd; R-515BYes——Yes2026-11-11
Hitachi Cooling & Heating—12,3102Two-stage centrifugal (S, VG); oil-free magnetic-levitation (VM)R-513A; R-1233zd; R-1234ze; R-134a————2026-11-11
Daikin Applied302110,5511Variable-volume-ratio screw; Variable-speed oil-free magnetic-bearingR-1234ze(E); R-515B; R-513A; R-1233zd(E)Yes29.41——2026-11-11
Dunham-Bush264110,5501Inverter-driven dual-stage, oil-free magnetic-bearingR-134a; R-513A————2026-11-11
Vertiv30016,0004Inverter screw; oil-free magnetic-levitation centrifugalR-1234ze; R-513A; R-515B; R-134aYes——Yes2026-11-11
Carrier17013,8001Scroll; variable-speed screw; two-stage magnetic-bearing centrifugalR-513A; R-1234ze(E); R-515B; R-32Yes3531802Yes2026-11-11
Johnson Controls (YORK)88043,5004Single-stage magnetic-bearing centrifugal, variable-speedR-1234ze—3031801Yes2026-11-11
Multistack—2,9891Two-stage variable-speed centrifugal MagLev—Yes———2026-11-11
Smardt21112,5001Oil-free magnetic-bearingR-513A; R-515B; R-1234ze; R-134aYes———2026-11-11
Uniflair (Schneider Electric)1,20012,5001Oil-free magnetic-bearing centrifugal—Yes3311801Yes2026-11-11
Midea Building Technologies56312,2511Two-stage magnetic-bearing centrifugal; inverter screwR-1234ze(E); R-513AYes——Yes2026-11-11
Geoclima (Munters)—2,2001Oil-free centrifugal Turbocor with magnetic levitationR-513A; R-134A; R-1234zeYes———2026-11-11
LG Electronics1,68812,1101Semi-hermetic oil-free magnetic-bearing centrifugal, variable-speedR-513AYes——Yes2026-11-11
Airedale by Modine11012,0002Oil-free centrifugal TurbocorR-1234ze; R-134aYes262——2026-11-11
ENGIE Refrigeration25012,0001Oil-free magnetic-bearing—Yes———2026-11-11
STULZ28011,8601Screw (stepless or frequency-converter); TurbocorR-1234ze; R-513AYes251——2026-11-11
Kaltra25011,8501Screw; scrollR-134a; R-513A; R-1234ze; R-410A; R-452B; R-454BYes———2026-11-11
Mitsubishi Electric (Climaveneta)1,20011,7501Magnetic-levitation centrifugal; oil-free magnetic-bearingR-1234ze; R-515BYes263—Yes2026-11-11
Aermec20011,6001Screw (NSM HWT); Turbocor magnetic-levitation (TBA/TBG)R-134a; R-513A; R-1234ze; R-515B; R-32Yes301——2026-11-11
Euroklimat19011,4001Oil-free magnetic-levitation TurbocorR-134a; R-513A; HFO optionYes———2026-11-11
Galletti37011,2001Hermetic scrollR-410AYes———2026-11-11
Swegon (BlueBox)22014801ScrollR-32Yes201——2026-11-11
Clivet——Magnetic, full inverter—Yes———2026-11-11

The lines behind each row

All 32 vendors

How to read the columns

Methodology
Smallest unit kW
Lowest published cooling capacity across the chiller lines named in the 'Lines' field, converted from refrigeration tons at 3.517 kW per ton where the vendor publishes tons. Rating conditions differ by vendor and line, so compare ranges, not decimals. Blank when no line states a lower bound.
Largest unit kW
Highest published cooling capacity of a single chiller across the lines named in 'Lines', converted from tons at 3.517 kW per ton where needed. Project totals, multi-unit plants and announced-only products are excluded. Blank when not published.
Compressors
Compressor technologies in the named lines, as the vendor words them: scroll, screw, centrifugal, magnetic-bearing (oil-free) centrifugal.
Refrigerants
Refrigerants the vendor lists for the named lines. A refrigerant may be offered only on some sizes or markets; the record's sources say which.
Free cooling
The vendor offers integrated or optional free cooling (outside air or a water-side economiser) on at least one named line. It does not mean the compressors stay off all year.
Max supply water °C
Highest chilled-water supply (leaving) temperature the vendor states for a named line. A rating point is not an operating limit and is not used here. Blank when not stated.
Full-load recovery s
Seconds from a power interruption to full cooling output, as the vendor states it for a named line.
AI or high-density claim
The vendor names AI, high-density or liquid-cooled data centers as a target of a named line, on a page cited in the record's sources. Blank means no such claim was found on the pages read.